Note that you need the updated file "IncFiles/SystemResDX.inp" in order to set
SUPPLY-MTR-CLASS using the global parameter SupplyMtrClass.
When you install this file, other DEER measures may no longer work correctly,
because MASControl3 does not define "SupplyMtrClass" for those measures.



Find these keywords by editing and saving a model in eQuest, or confer DOE2 manuals,
Volume 2: Dictionary > HVAC Components > SYSTEM > Air Flow and Fans > Supply Fan.
*SUPPLY-KW/FLOW
*FAN-CONTROL
*FAN-EIR-FPLR
*SUPPLY-MTR-CLASS


Possible values for SUPPLY-KW/FLOW:
Number in kW/CFM, typically 0.000200 to 0.000700

Where to find SUPPLY-KW/FLOW in existing:
For SFm: MASControl3\IncFiles\SystemResDX.inp
Currently set by product of two parameters,
{ #PA("FanWPerCfm") * #PA("FanPwrMult")/1000 }



Possible values for SUPPLY-MTR-CLASS:
STANDARD
HI-EFF
PREMIUM

Where to find SUPPLY-MTR-CLASS existing:
For SFm: Set by default; no parameters defines it in DEER 2020.

Where to set SUPPLY-MTR-CLASS:
Create New global parameter for SUPPLY-MTR-CLASS:
SupplyMtrClass

Where does it apply:
For example, for SFm (MASControl3/Templates/SFm_DX_SZ.INP)
The new keyword will apply to each of
SYSTEM_A1
SYSTEM_A2
SYSTEM_B1
SYSTEM_B2